R602.10.4.4 Continuously Sheathed Braced Wall Panel Location and Corner Construction
Go To Full Code Chapter
For all continuous sheathing methods, full-height braced wall panels complying with the length requirements of Table R602.10.4.2 shall be located at each end of a braced wall line with continuous sheathing and at least every 25 feet (7620 mm) on center. A minimum 24 inch (610 mm) wood structural panel corner return shall be provided at both ends of a braced wall line with continuous sheathing in accordance with Figures R602.10.4.4(1) and R602.10.4.4(2). In lieu of the corner return, a hold-down device with a minimum uplift design value of 800 pounds (3560 N) shall be fastened to the corner stud and to the foundation or framing below in accordance with Figure R602.10.4.4(3).
Exception:
The first braced wall panel shall be permitted to begin 12.5 feet (3810 mm) from each end of the braced wall line in Seismic Design Categories A, B and C and 8 feet (2438 mm) in Seismic Design Categories D0, D1 and D2 provided one of the following is satisfied:
- A minimum 24 inch (610 mm) long, full-height wood structural panel is provided at both sides of a corner constructed in accordance with Figure R602.10.4.4(1) at the braced wall line ends in accordance with Figure R602.10.4.4(4), or
- The braced wall panel closest to the corner shall have a hold-down device with a minimum uplift design value of 800 pounds (3560 N) fastened to the stud at the edge of the braced wall panel closest to the corner and to the foundation or framing below in accordance with Figure R602.10.4.4(5).
Related Code Sections
R602.10.4.4 Wall Construction, Continuously Sheathed Braced Wall Panel Location and Corner Construction
For all continuous sheathing methods, full-height braced wall panels complying with the length requirements of Table R602.10.4.2 shall be located ...
R602.10.2.2 Wall Construction, Locations of Braced Wall Panels
Braced wall panels shall be located at each end of a braced wall line. Exception:
Braced wall panels constructed ...
R602.10 Wall Construction, Wall Bracing
SHEATHING WITH CORNER RETURN PANEL
For SI: 1 inch = 25.4 mm, 1 pound = 4.448 N.
FIGURE R602.10.4.4(3) BRACED WALL LINE WITH CONTINUOUS ...
R613.5.3 Wall Construction, Wall Bracing
SIP walls shall be braced in accordance with Section R602.10. SIP walls shall be considered continuous wood structural panel sheathing for purposes ...
R610.5.5 Wall Construction, Wall Bracing
SIP walls shall be braced in accordance with Section R602.10. SIP walls shall be considered continuous wood structural panel sheathing (bracing ...